|     | Advanced search
Print this page | Send this page

e-Business & Resilience Centre (eBRC)

e-Business & Resilience Centre (eBRC)eBRC
Goldbell Center, Tour A
5, rue Eugène Ruppert
L-2453 Luxembourg
Phone: +352 26 06-1
Fax: +352 26 06 20 90

http://www.ebrc.lu

 

Locations

  • Luxembourg-Gasperich (Hitec Centre, Resilience Centre)
  • Windhof
  • Kayl (Resilience Centre - 2010)

Design

  • Tier 3+ (Hitec Centre)
  • Tier 4 (Resilience Centre Windhof, Resilience Centre Kayl)

Size

  • 2009: 6.500 m²
  • 2010: 11.500 m²

IT room height

  • Hitec Centre: 2,70 m
  • Resilience Centre Windhof: 3,40 m
  • Resilience Centre Kayl: 3,50 m

Raised floor

  • Hitec Centre: 0,50 m
  • Resilience Centre Windhof: 1 m
  • Resilience Centre Kayl: 1 m

Floor charge

  • Hitec Centre: 1.500 kg/m2
  • Resilience Centre Windhof: 1.500 kg/m2
  • Resilience Centre Kayl: 2.000 kg/m2

Equipment elevator

  • Hitec Centre: 2.500 kg
  • Resilience Centre Windhof: 3.500 kg
  • Resilience Centre Kayl: 3.500 kg

UPS systems

  • Hitec Centre: 2*N redundant D-UPSs + integrated Diesel power (short break) generator
  • Resilience Centre Windhof: 2*(N+1) redundant D-UPSs + Diesel power (short break) generator
  • Resilience Centre Kayl: 2*(N+1) redundant D-UPSs + Diesel power (short break) generator

Generator autonomy

96 hours

Electrical power to IT rooms

  • Hitec Centre: 600 to 720 W/m2
  • Resilience Centre Windhof: 750 to 1.000 W/m2
  • Resilience Centre Kayl: 1.000 to 4.000 W/m2

Cooling specifications

  • Hitec Centre: air cooling chain 600 to 720 W/m2
  • Resilience Centre Windhof: air and water cooling chain 750 to 1.000 W/m2
  • Resilience Centre Kayl: air and water cooling chain 1.000 to 4.000 W/m2

Cooling redundancy

  • Hitec Centre: 2*N
  • Resilience Centre Windhof: 2*(N+1)
  • Resilience Centre Kayl: 2*N+1

Infrastructure security

  • 24x7x365 local and remote central monitoring of all technical and security systems
  • Integral and redundant fire detection system (air sampling system)
  • Redundant neutral gas fire suppression system
  • Lightning protection system
  • Water leakage detection

Site security and safety

  • 24x7x365 on site security guards
  • 24x7x365 remote central monitoring of all technical and security systems
  • Intrusion Detection System
  • Dedicated access control system
  • CCTV with digital recorder

Telehouse

  • 100% resilient with high speed connectivity
  • 2 physically separate Telecom rooms in every building
  • International Telecom providers / Multiple local carriers
  • Large choice of Internet suppliers

Information provided by eBRC.